Protective earth

Protective earth 1:

The protective earth is established via the left-hand earthing bolt on the power supply module and the mounting plate on the control cabinet. The connection is made via a cable with a ring-shaped cable lug [1].
The safety standard for electrical power drive systems (PDS), IEC/DIN EN 61800-5-1, specifies that for permanently connected devices with elevated leakage currents, a protective conductor with a cross-sectional area of at least 10 mm² must be connected. If the protective conductor of the device's power supply is less than 10 mm², an additional protective conductor must be connected.

Optionally, an additional protective earth can be attached via the right-hand earthing bolt of the last module.

►Make up a cable with a ring-shaped cable lug and a cross-section of at least 10 mm²


Protective earth 2:
►Plug the cable with the cable lug [1] onto the left-hand earthing bolt [2] of the first module in the drive system


Protective earth 3:
►Place nut [3] on the earthing bolt [2] on top of the cable lug [4] and screw it tight
►Do not use a spring washer [5]
►Observe tightening torques:

Components

Tightening torque [Nm]

Serrated hexagonal nut
M5, strength class A2-50

2.7

►Attach the assembled cable properly to the control cabinet mounting plate. Clean the contact surfaces prior to the installation and ensure that the mounting plate is not painted.