Module connection
The connection of the individual modules in a drive system takes place via the grounding hangers [1]. These are each mechanically fixed to the right-hand earthing bolt of the module and swiveled onto the left-hand earthing bolt of the adjacent module. They are mechanically locked by the nuts and the serrations.
- ►Plug the grounding hanger [1] onto the earthing bolt [2] of the right-hand module
- ►Make sure that the opening in the grounding hanger [1] is facing upwards
- ►Screw the nut [3] on the grounding bolt [2] onto the grounding hanger [1]
- ►Do not use a spring washer [4]
- ►Swivel the grounding hanger [1] onto the earthing bolt [5] of the left-hand module
- ►Screw the nut [6] on the grounding bolt [5] onto the grounding hanger [1]
- ►Do not use a spring washer [7]
- ►Tighten both nuts firmly
- ►Observe tightening torques:
Components | Tightening torque [Nm] |
|---|---|
Serrated hexagon nut | 3.5 |
- ►Mount further grounding hangers [8]