Module connection
The connection of the individual modules in a drive system takes place via the grounding hangers [1]. These are each mechanically locked to the right-hand earthing bolt of the module and swiveled onto the left-hand earthing bolt of the adjacent module, where they are mechanically locked by the nuts and serrations.
- ►Push the grounding hanger [1] onto the earthing bolt [2] of the right-hand module
- ►Make sure that the opening in the grounding hanger [1] is facing upwards
- ►Screw the nut [3] onto the earthing bolt [2] on top of the grounding hanger [1]
- ►Do not use a spring washer [4]
- ►Swivel the grounding hanger [1] onto the earthing bolt [5] of the left-hand module
- ►Screw the nut [6] onto the earthing bolt [5] on top of the grounding hanger [1]
- ►Do not use a spring washer [7]
- ►Tighten both nuts firmly
- ►Observe tightening torques:
Components | Tightening torque [Nm] |
|---|---|
Serrated hexagonal nut | 2.7 |
- ►Mount [8] further grounding hangers