Practical example

The configured 480 V DC drive system consists of:

Number

Component

4

Servomotors from the AM8031-0D21 series with cable lengths of 4 m, 10 m, 15 m and 22 m

4

Servomotors from the AM8051-0G21 series with cable lengths of 16 m, 18 m, 21 m and 25 m

4

Dual-axis modules from the AX8206 series

1

Power supply modules from the AX8620 series

Total standstill current I0

The total standstill current I0 relates to all servomotors listed in the practical example and corresponds to:

The total standstill current I0 is now multiplied by the simultaneity factor. In the case of a machine tool this is relatively high, e.g. 0.9, because all axes can drive into the material at the same time. In the case of a handling system the factor is more likely to be 0.7. This then corresponds to:

The AX8620 power supply module was selected on the basis of the calculations.

 

24 VDC current consumption

The 24 V DC current consumption relates to all the components listed in the practical example and corresponds to:

Result

The maximum single cable length for the AM8051-0G21 is 25 m and is thus ≤ 25 m

The total cable length of all servomotors is 131 m and is thus ≤ 300 m

The 24 V DC current consumption of all components is 5.88 A DC and is therefore ≤ 20 A DC

The maximum DC link capacitance is always related to the connection to a common AX8620 power supply module with 945 µF and is thus ≤ 6000 µF