Voltage testing and insulation resistance measurement
Factory testing
All AX8000 series devices are voltage tested in the end of line test in accordance with the requirements for routine testing of product standard 61800-5-1 to prove that air gaps in the basic isolation and reinforced isolation have not been reduced during manufacture.
Testing provided by the customer
AX8000 components may be damaged if the machine or system is tested by the customer!
![]() | To protect the components, all device connections must be disconnected before a voltage test or insulation resistance test. |
