AX81xx-0x20 with 1 x D-sub
A D-sub connector (X11) is available for the AX81xx-0x20 single-axis modules.
Typical applications
- as primary feedback, for example as a commutation encoder for linear motors and third-party motors
- as secondary feedback to increase accuracy when OCT is used as primary feedback.
Supported digital and analog feedback protocols:
- EnDat® 2.2/22
- BiSS® C
- TTL (DIFF RS422)
- SinCos 1 Vpp
Pin assignment X11
Pin | EnDat® 2.2/22 | BiSS® C | TTL | SinCos |
|---|---|---|---|---|
1 | n.c. | n.c. | n.c. | SIN |
2 | GND | GND | GND_5 V | GND_5 V |
3 | n.c. | n.c. | n.c. | COS |
4 | 5 V DC±10% | 5 V DC±10% | 5 V DC±10% | 5 V DC±10% |
5 | Data; DX+ | Data+ / SLO+ | B+ | n.c. |
6 | Us 11 V DC 1) | Us 11 V DC 1) | Us 11 V DC 1) | Us 11 V DC 1) |
7 | n.c. | n.c. | REF Z | REF Z |
8 | Clock; CLK+ | CLK+ / MA+ | A+ | n.c. |
9 | n.c. | n.c. | n.c. | REFSIN |
10 | GND sense | GND sense | GND sense | GND sense |
11 | n.c. | n.c. | n.c. | REFCOS |
12 | 5 V sense | 5 V sense | 5 V sense | 5 V sense |
13 | Data; DX- | Data- / SLO- | B- | n.c. |
14 | n.c. | n.c. | Z | Z |
15 | Clock; CLK- | CLK- / MA- | A- | n.c. |
1) When using encoders with 11 V DC supply voltage (pin 6), the sense pins (10 and 12) must not be assigned.
Only one protocol can be set per module.
Maximum output current per D-sub connector: 250 mA
Cut-off frequency SinCos 1 Vpp: 270 kHz
Cut-off frequency TTL (DIFF RS422): 10 MHz