AX8600 Power supply module DC
| |
Warning of high voltage! Even after shutdown of the mains voltage, a life-threatening DC link voltage can be present at the contacts of the AX8000 system for up to 30 minutes. Before removing the connector [1] of the ZK4875-900x DC link connection cable, the following action steps must be observed:
|
Notice | |
Possible loss of IEC and UL approval The AX8600 DC power supply module and the DC link connection cable may only be used within the AX8000 system. Connecting third-party equipment to the cable or feeding DC voltage from an external source is not covered by the IEC and UL approval of the components. |
If, for example, an AX8000 multi-axis servo system is to be coupled with another system in the DC link in a multi-row set-up, you can implement this case using a ZK4875-900x-zzzz DC link connection cable and an AX8600 DC power supply module. The plug of the DC link connection cable [1] is connected to the AX-Bridge of the last AX8000 axis module [2] and the plug [3] in the next row is connected to the AX8600 [4].