ZS4500 - I/O plug connector

Technical data

Technical data

ZS4500-2006

ZS4500-2007

ZS4500-2008

Number of terminal points

10

10

30

Signal LEDs

no

yes

yes

Nominal voltage

24 VDC

24 VDC

24 VDC

Rated current

2 A

Wire cross section

0.5 mm2 ... 1.5 mm2

Length of stripped conductor

10 mm

Dimensions (W x H x D)

approx. 42mm x 10.3mm x 26.9mm

approx. 42mm x 12.7mm x 26.9mm

approx. 42mm x 20.8mm x 26.9mm

Weight

approx. 10 g

approx. 10 g

approx. 20 g

Operating temperature

0°C... + 55°C

Storage temperature

-25°C... + 85°C

Relative humidity

95%, no condensation

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP 20

Installation position

variable

Approval

CE, UL, CSA

Ordering information for I/O plug connectors

Order designation

Signal LEDs

Supports the following connection types

Single-conductor

Two-conductor

Three-conductor

ZS4500-2006

no

yes

no

no

ZS4500-2007

yes

yes

no

no

ZS4500-2008

yes

yes

yes

yes

Connection of digital sensors/actuators

ZS4500-2006 (standard) and ZS4500-2007 (optional)

The connection type (single-conductor) in the two connectors ZS4500-2006 and ZS4500-2007 is identical. The ZS4500-2007 is additionally equipped with LEDs.The following diagram shows the ZS4500-2006.

ZS4500 - I/O plug connector 1:

A sensor (F) is connected at terminal point "0" via a single-conductor connection. The 24 V supply for the sensor is connected externally. The 24 V supply for the sensor (F) could be taken directly from terminal point "24", although this would preclude further connections since only one 24 V connection can be connected at terminal point "24".

In this case terminal point "7" is configured as an output. The configuration is implemented on the software side. At this point a relay (G) is connected via a single-conductor connection. The 0 V connection is established externally. Terminal point "0V" can only be used once.

ZS4500 - I/O plug connector 2:

Ground potential

    • If sensor (F) or further initiators are supplied through a separate power supply unit, the ground potential of the separate power supply unit must be connected with the ground potential of terminal point "GND" of connector "X03" (24 V supply).
    • The ground potential (0 V) of the relay (G) must be connected with the ground potential of terminal point "GND" of connector "X03" (24 V supply).

    ZS4500-2008 (optional)

    A single-, two- or three-conductor connection may be used for this connector. The diagram shows the two- and three-conductor type. The single-conductor type matches the diagram for connector ZS4500-2006.

    ZS4500 - I/O plug connector 3:

    The terminal points at (B) are internally bridged. The two bridges (A) must be established externally on the connector to ensure the required function.

    A sensor (C) is connected at terminal point "2" via a two-conductor connection.

    A sensor (D) is connected at terminal point "4" via a three-conductor connection.

    In this case terminal point "7" is configured as an output. The configuration is implemented on the software side. At this point a relay (E) is connected via a two-conductor connection.