Error reset (command S-0-0099)
After rectifying an error, it is necessary to perform an error reset. The associated command is the IDN S-0-0099. This command can also be given directly via the display. As soon as an error occurs the display flashes continuously; the standard display is shown again and the flashing stops only after a successful error reset.
Overview

Executing the command
Press the right side of the rocker
3x until the following display appears: 
|
Display |
Description |
|---|---|
|
|
1 = "M" indicates that the "menu mode" is activated. |
There are now 2 possibilities:
Press the center of the rocker
for approx. 3 sec. to execute the reset command for channel "A"
or
Press the upper or lower side of the rocker
and switch to channel "B". Now press the center of the rocker
for approx. 3 seconds and execute the Reset command for channel "B". The following display appears
.
The standard display should appear again after approximately 25 seconds. If the error display is still visible after that, this means that you have not rectified the cause of the error, or that there are further errors.