Sync1
The “Sync1” signals are parameterized according to the NC cycle time as standard. This cycle time is always a multiple of Sync0. If a signal is missing (see F1), the CPU also generates error code F414, and the connected axes are brought to a stop using the “EStop ramp”.
Additional error messages:
The Sync1 cycle time must be a multiple of the Sync0 cycle time and must be identical to the parameters “S-0-0001 and S-0-0002”, otherwise the CPU generates the error code F412.
If the signal “Sync1” is not activated in the ESC, the CPU generates the error code F413.
If the pulse length of the interrupt no longer conforms to the standard, the CPU generates the error code F411.
In the case of each error message the connected axes are brought to a standstill with the “EStop ramp”.
The fastest AX5000 I/O update time is 250 µs. All controllers (current controller, speed controller and position controller) are calculated with up to 62.5 µs.