Sync0

The "Sync0" signals are sent every 250 µs as standard. If a signal fails to materialize, the CPU generates the error code F414, and the axes of the servo drive are stopped with the "EStop ramp".

Additional error messages:
The Sync0 cycle time may only be configured with 62.5 µs, 125 µs or 250 µs, otherwise the CPU generates the error code F409.
If the signal "Sync0" is not activated in the ESC, the CPU generates the error code F410.
If the pulse length of the signal no longer conforms to the standard, the CPU generates the error code F411.
In the case of each error message the axes are brought to a standstill with the "EStop ramp".