Technical data

Technical data

ZS4500-2006

ZS4500-2007

ZS4500-2008

Number of terminal points

10

10

30

Signal LEDs

no

yes

yes

Rated voltage

24 VDC

24 VDC

24 VDC

Rated current

2 A

Wire cross section

0.5 mm2 ... 1.5 mm2

Strip length

10 mm

Dimensions (W x H x D)

approx. 42mm x 10.3mm x 26.9mm

approx. 42mm x 12.7mm x 26.9mm

approx. 42mm x 20.8mm x 26.9mm

Weight

approx. 10 g

approx. 10 g

approx. 20 g

Permissible ambient temperature range during operation

0°C ... + 55°C

Permissible ambient temperature range during storage

-25°C ... + 85°C

Permissible relative humidity

95 %, no condensation

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP 20

Installation position

variable

Approval

CE, UL, CSA