X03: 24 V DC supply

System and peripheral voltage for the servo drive is supplied via connector X3. The supply is configured as a 2-channel system in order to offer an option to separate between motor holding brakes and control electronics.

CAUTION

Safe operation!

The voltage tolerances must be taken into account when connecting motors with holding brake.

X03: 24 V DC supply 1:

Terminal point

Connection

Current consumption

Wire cross-section

Tightening torque of the terminal points

Up

24 VDC ±10% (depending on the motor holding brake) - peripheral voltage (e.g. separate brake supply)

Depending on the connected loads (see X06 and X14, X24)

 

 

Max. 6 mm²




0.5 Nm…0.6 Nm

Us

24 VDC-15% + 20% - system supply voltage

-12 A = 0.4 A…0.8 A
18 A…25 A = 1.1 A
40 A = 1.6 A

GND

GND

 

Connection to the standard supply network 24 VDC (X03)

The 24 VDC connection “X03” is used for supplying the control electronics and periphery with DC voltage. The control electronics and the periphery can be supplied separately with two different voltage sources.

X03: 24 V DC supply 2:

If one power supply unit is used for the 24 VDC power supply, the connections US and UP must be bridged, in order to ensure that both the control electronics and the periphery are supplied.

Supply via one or two power supply units

X03: 24 V DC supply 3: