Fuse protection
External protection, CE-compliant
| |
Fire hazard due to overload of the connection cable!
|
Single-phase:
| AX5101 | AX5103 | AX5106 | AX5201 | AX5203 | AX5206 |
---|---|---|---|---|---|---|
AC supply *) | 10 AT | 10 AT | 16 AT | 10 AT | 16 AT | 20 AT |
24 V supply | 5 AT | |||||
Braking resistor | electronic |
*) Application class "gG" mains fuses according to IEC 60269 or "C" type automatic circuit-breakers must be used.
Three-phase:
|
AX5101 |
AX5103 |
AX5106 |
AX5112 |
AX5118 |
AX5125 |
AX5140 |
AX5201 |
AX5203 |
AX5206 |
---|---|---|---|---|---|---|---|---|---|---|
AC supply *) |
6 AT |
6 AT |
10 AT |
20 AT |
35 AT |
35 AT |
50 AT |
10 AT |
10 AT |
20 AT |
24 V supply |
5 AT | |||||||||
Brake resistor |
electronic |
*) Application class "gG / gL" mains fuses according to IEC 60269 or "C" type automatic circuit-breakers must be used.
Internal protection, CE-compliant
Circuit | Fuse |
---|---|
24 V system voltage | 3.4 AF |
24 V peripheral voltage | electronic |
Braking resistor | electronic |
External protection, UL-compliant
The integrated protection against short circuit is no substitute for the external mains protection. The mains protection must comply with the vendor's specification and the national and international regulations and laws.
Can be used in power supply systems with a maximum current carrying capacity of 18000 A at 480 V.
For alternatives to UL Class RK5 fuses, be sure to refer to UL Standard UL 508 A, Chapter SB4.2.3, Exception No. 1. For further questions regarding UL fuses, please contact the appropriate certificate authority.
Single-phase:
| AX5101 | AX5103 | AX5106 | AX5201 | AX5203 | AX5206 |
---|---|---|---|---|---|---|
AC supply (max.) *) | 6 A | 12 A | 20 A | 12 A | 20 A | 20 A |
24 V supply (max.) | 3 A | |||||
Braking resistor | electronic |
*) Only UL approved line fuses are to be used.
Three-phase:
| AX5101 | AX5103 | AX5106 | AX5112 | AX5201 | AX5203 | AX5206 |
---|---|---|---|---|---|---|---|
AC supply (max.) *) | 6 A | 12 A | 20 A | 20 A | 12 A | 20 A | 20 A |
24 V supply (max.) | 3 A | ||||||
Braking resistor | electronic |
*) Only UL-approved mains fuses must be used.
NOTICE | ||
![]() | AX5112! Protection only by UL-approved fuses with a nominal current of 20 A and 480 V min. |
Internal protection, UL-compliant
Circuit | Fuse |
---|---|
24 V system voltage | 3.4 AF |
24 V peripheral voltage | electronic |
Braking resistor | electronic |
External drive system protection
Rule of thumb: | Determine the nominal sum currents of the devices, multiply with the correction factor and round up to the next higher standard level. |
Example: | 1 x AX5103 + 2 x AX5201 + 2 x AX5203 |
NOTICE | ||
![]() | Special requirements for a drive system Please consult our applications department with respect to the special requirements for a drive system with UL approval. |
Residual current circuit breaker
Servo drives with built-in mains filters generate a small leakage current (fault current) due to the capacitors in the filter. This fault current is responsible for malfunctions in standard residual current circuit breakers. For this reason so-called AC/DC sensitive residual current circuit breakers must be used, which also take into account DC currents.