Configuration of jumpers J-"A" for channel "A" and J-"B" for channel "B"

Jumpers J-“A” and J-“B” (1) are located at the center of the printed circuit board near the front panel of the card. For each channel there are 2 rows of jumpers, each with 20 pins. The default setting without analysis of the additional inputs is shown in the following figure.
The opposite figure shows the basic jumper configuration, which is the same for channel A and channel B. The corresponding pins of input sockets X41 and X42 are permanently wired to the corresponding pins of the jumper rows. The non-configurable pins are not shown. To use the additional inputs proceed as follows:
- Reposition the relevant jumpers and set IDN P-0-0180-->Feedback options-->Digital Inputs “Input A” to “Input D” to “used” or set IDN P-0-0180-->Feedback options-->Digital Inputs “Input E” or “Input F” to “used” without repositioning the jumpers.
- Wire the encoder cable as required for the relevant inputs or use an adapter.
The following table shows a selection of combination options.
Feedback system | Input “A” | Input “B” | Input “C” | Input “D” | Input “E” | Input “F” |
|---|---|---|---|---|---|---|
EnDat® | Input A-F not available | |||||
BiSS® | Input A-F not available | |||||
Hiperface® | X | X |
|
|
|
|
Sin/Cos | X | X | X | X |
|
|
TTL1) | X2) | X2) | X3) | X3) | X2) | X3) |
1) Attention: Wire break detection is not supported for TTL encoders!
2) Either inputs “A” and “B” or input “E” can be used.
3) Either inputs “C” and “D” or input “F” can be used.