Mounting sequence and circuit diagram

Mounting sequence and circuit diagram 1:

Observe the mounting sequence:

 

Observe the order of connection:

Connect the mains choke to the supply network.

DANGER

Serious risk of injury through high electrical voltage!

Due to the DC link capacitors, the DC link contacts “DC+ and DC-” and “RB+ and RB-” may be subject to life-threatening voltages exceeding 875 VDC, even after the servo drive was disconnected from the supply network.
For the AX5160/AX5172, wait 15 minutes; for the AX5190/AX5191, wait 30 minutes; and for the AX5192/AX5193, wait 45 minutes after disconnecting. Measure the voltage on the DC links DC+ and DC-. Safe working is possible once the voltage has fallen below 50 V.