Serious risk of injury from electric shock! Only qualified electricians are permitted to perform the wiring for the braking resistors. - Check the assignment of the servo drive and the braking resistor. Compare the rated voltage and the rated current of the devices.
- Always make sure that the braking resistors are de-energized during assembly and wiring, i.e. no voltage may be switched on for any piece of equipment which is to be connected. Ensure that the control cabinet remains turned off (barrier, warning signs etc.). The individual voltages will only be turned on again during commissioning.
- Due to the DC link capacitors, the DC link contacts “DC+ and DC-” and “RB+ and RB-” may be subject to life-threatening voltages exceeding 875 VDC, even after the servo drive was disconnected from the supply network.
Wait 5 minutes for the AX5101 – AX5125 and AX520x; 15 minutes for the AX5140/AX5160/AX5172; 30 minutes for the AX5190/AX5191; 45 minutes for the AX5192/AX5193 after disconnecting, and measure the voltage at the DC links „DC+ and DC-“. Safe working is possible once the voltage has fallen below 50 V.
|