Connection the brake resistor

Remove the two screws (1) and remove the cover (2) in direction of the arrow. Connect an adequately dimensioned cable (see chapter “Cables”) to the connections (3) of the resistor and the grounding bolt (5) and take it out of the terminal box through the strain-relief assembly (9). Ensure adequate strain relief with the two screws (8). Connect the other side of the cable to the DC link contact connector “X2” of the AX5000. The connector is supplied with the AX5000. Connect the grounding cable to the grounding conductor of the control cabinet.

Connect an adequately dimensioned cable to the potential-free normally closed contact (4) of the temperature switch and take it out of the terminal box through the strain-relief assembly (7) (see chapter “Temperature switch”). Ensure adequate strain relief with the nut (6).

Install the cover (2) in reverse order.

Connection the brake resistor 1:
Connection the brake resistor 2: