Mounting positions and distances

(A) = vertical installation is only permitted according to the diagram (terminal box facing downwards).
(B) = horizontal installation

 

Assignment of the device classes

Mounting positions and distances 1:

 

Mounting positions and distances 2:

 

For all installation positions the following minimum distances must be adhered to:

200 mm to adjacent components, walls, etc. and 300 mm to components, ceilings, etc. located above. In the case of vertical installation (A), a distance of 200 mm must be maintained to components located underneath to ensure that air can flow without hindrance to the braking resistor.