General overview

General overview 1:

No.

Name

1

Navigation rocker

2

Labeling field

3

X05 – socket for EtherCAT output

4

X03 – power supply 24 V DC
           Input

5

X52 – connection of the temperature monitor
           and the fan of the
           external braking resistor

6

X51 - connection of the external braking
           resistor

7

X01 – mains supply
           100…480 V

8

X02 - DC link output
           (875 V DC voltage)

9

General overview 2:

DANGER

Max. 875 V DC voltage at the DC link terminals X02. 15 minutes after shutdown of the device, life-threatening voltage is still present. Safe working is possible once the voltage has fallen below 50 V.

10

X04 – socket for EtherCAT input

11

Display