Serious risk of injury through high electrical voltage! - Never open the servo drive when it is live. Wait until the DC link capacitors are discharged. The measured voltage between the terminals "DC+ and DC-" and "RB+ and RB-" must have dropped below 50 V. Opening the device (with the exception of expansion card slots) invalidates all warranty and liability claims against Beckhoff Automation GmbH & Co. KG.
- Negligent, improper handling of the servo drive and bypassing of the safety devices can lead to personal injury or death through electric shock.
- Ensure that the protective conductor is connected properly.
- Disconnect the servo drive from the supply network and secure it against reconnection before connecting or disconnecting the pluggable terminals.
- Disconnect the servo drive from the supply network and secure it against reconnection before working on electrical parts with a voltage > 50 V.
- Due to the DC link capacitors, the DC link terminal points "DC+ and DC-" and "RB+ and RB-" may be subject to dangerous voltages exceeding 875 VDC, even after the servo drive was disconnected from the supply network. Wait 5 minutes for the AX5101 - AX5125 and AX520x; 15 minutes for the AX5140/AX5160/AX5172; 30 minutes for the AX5190/AX5191; 45 minutes for the AX5192/AX5193 after disconnecting, and measure the voltage at the DC link terminal points "DC+ and DC-". The device is safe once the voltage has fallen below 50 V.
|