External protection for individual devices, CE-compliant
| |
Fire hazard due to overload of the connection cable!
|
Single-phase
|
|
AX5101 |
AX5103 |
AX5106 |
AX5201 |
AX5203 |
AX5206 |
|---|---|---|---|---|---|---|
|
AC supply*) |
10 A |
10 A |
16 A |
10 A |
16 A |
20 A |
|
24 V DC supply |
5 AT | |||||
|
Braking resistor |
electronic | |||||
*) Mains fuses of class “gG” or circuit breakers with characteristic “C” must be used.
Three-phase
|
|
AX5101 |
AX5103 |
AX5106 |
AX5201 |
AX5203 |
AX5206 |
|---|---|---|---|---|---|---|
|
AC supply *) |
6 A |
6 A |
10 A |
10 A |
10 A |
20 A |
|
24 V DC supply |
5 AT | |||||
|
Braking resistor |
electronic | |||||
|
|
AX5112 |
AX5118 |
AX5125 |
AX5140 |
|---|---|---|---|---|
|
AC supply *) |
20 A |
35 A |
35 A |
50 A |
|
24 V DC supply |
5 AT | |||
|
Braking resistor |
electronic | |||
*) Mains fuses of class “gG” or circuit breakers with characteristic “C” must be used.
Internal protection, CE-compliant
|
Circuit |
Fuse |
|---|---|
|
24 V DC system voltage |
3.4 AF |
|
24 V DC peripheral voltage |
electronic |
|
Braking resistor |