X03: 24 VDC supply
System and peripheral voltage for the servo drive is supplied via connector X3. The supply is based on two channels in order to offer an option to separate between motor holding brakes and control electronics.
| |
Safe operation! The voltage tolerances must be taken into account when connecting motors with stopping brake. |
| Terminal point | Connection | Current consumption | Wire cross-section |
|---|---|---|---|---|
| Up | 24 VDC ±10% (depending on the motor holding brake) - peripheral voltage (e.g. separate brake supply) | Depending on the connected consumers (see X06 and X14) | Max. 6mm² |
Us | 24 VDC-15% + 20% - system supply voltage | 60A – 72A = 3A | ||
GND | GND | |||
Connection to the standard supply network 24 VDC (X03)
The 24 VDC connection "X03" is used for supplying the control electronics and periphery with DC voltage. The control electronics and the periphery can be supplied separately with two different voltage sources.
![]() | If one power supply unit is used for the 24 VDC power supply, the connections US and UP must be bridged, in order to ensure that both the control electronics and the periphery are supplied. |


