Transport and storage

Transport

Storage

Notice

Destruction of the equipment

On no account must the device be connected to 400 V if the DC link capacitors have lost their forming.
The capacitors must be reformed (see below).


> 5 years: The dielectric (an oxidation layer with a thickness of approx. 1 µ) in the DC link capacitors degrades over time, and the capacitors lose their forming.
Prior to commissioning of the servo drive the capacitors must be reformed. Release all electrical connections and feed the servo drive for about 30 minutes with 230 VAC (single-phase) at terminals L1/L2 or L2/L3.

Packaging