Typical error messages

Typical error messages 1:

If you are in the manual test menu and the position value (2) is grayed out, the cause is as follows: A “grayed out” actual position indicates a “WC state error” in EtherCAT drives. In this case, the WC state flag generated by the EtherCAT master is “true”, which means that the NC does not receive valid position data from the drive.

The corresponding EtherCAT drive is probably not in EtherCAT state “SafeOp” or “Op”. Further analysis is required to ascertain why the drive is not in this state.

 

Typical error messages 2:

To determine the exact cause, open the TCDriveManager via Configuration (3). In the status bar, another error code is shown at Diag Code (4). Check the drive state (5). Select Diagnostics (6) from the tree structure to get more information about the error. A list (7) on the right-hand side shows the complete error history. Update the list via the button with the two green arrows (8). Once the cause is identified and corrected, reset the axis via the R button (9)

 

Typical error messages 3:

After a brief moment, no error is displayed in the axis status line (10); the drive is ready for operation in the OP state (11). Update the list of error messages again (8). It should contain no more error messages (12)

 

Typical error messages 4:

In the manual test menu for the axis, the position value (13) is shown in black again.

Press the F8 button to acknowledge the NC error (14) in the manual test menu.

The drive is ready for operation again when the “Ready” flag is set.