Max. cable lengths including extensions
Rated motor voltage up to 400 V AC
Motor choke | AX5101…AX5112, AX52xx | AX5118, AX5125 | AX5140 | |||
|---|---|---|---|---|---|---|
C2 1) | C3 | C2 1) | C3 | C2 | C3 | |
Without | <25 m | <25 m | <25 m | <25 m | - | <30 m |
AX2090- | <100 m | <100 m | - | - | - | - |
AX2090- | - | - | <50 m | <50 m | - | - |
1) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0014.
2) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0032.
![]() | Sensitive sensors In exceptional cases (sensitive sensors, etc.) it can be necessary to use a motor choke even for motor cable lengths <25 m. |
Rated motor voltage up to 480 V AC
Motor choke | AX5101…AX5112, AX52xx | AX5118, AX5125 | AX5140 | |||
|---|---|---|---|---|---|---|
C2 1) | C3 | C2 2) | C3 | C2 | C3 3) | |
Without | <20 m | <20 m | <20 m | <20 m | - | 4) |
AX2090- | <100 m | <100 m | - | - | - | - |
AX2090- | - | - | <50 m | <50 m | - | - |
1) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0014.
2) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0032.
3) C3 with up to 70 m without mains choke possible for devices with order number AX5140-0000-1202.
4) Please contact our applications department
In exceptional cases (sensitive sensors, etc.) it can be necessary to use a motor choke even for motor cable lengths <20 m.
To keep line perturbations (distortion reactive power) as low as possible, a mains choke should always be used.
![]() | Malfunction in residential areas Mains chokes are products with restricted availability in accordance with EN 61800-3. The products may cause radio interference in residential areas. In this case, necessary measures must be taken by the operator. |