Connection of several servo drives to form a drive system
| Drive system with UL approval Please note the configuration example in chapter 5.2.4. |
| |
Destruction of the devices The connection sequence of the devices is not arbitrary. The rated sum current of the device must decrease from the mains supply onwards. AX5112, AX5106, AX5203, AX5201 = OK All devices in a drive system are always to be disconnected from and reconnected to the supply network together (emergency shutdown, mains contactor etc.). |
| |
Danger for persons and equipment Note the rated sum current of the connected devices. According to CE, the current-carrying capacity of the power busbars of the AX-Bridge is limited to 85 A. |
| |
Destruction of the external braking resistor An external braking resistor may not be connected to the X02 terminal point (DC link) in a drive system. Use an external brake module AX5021 for this. |