X12 - resolver / Hall
AX5160, AX5172, AX5190, AX5191, AX5192, AX5193

Pin | Resolver | analog Hall sensor |
|---|---|---|
1 | Temp. (only PTC, Klixon or bimetal!) | n.c. |
2 | AGND | n.c. |
3 | COS - (S3) | n.c. |
4 | SIN - (S4) | n.c. |
5 | REF - (R2) | n.c. |
6 | n.c. | SIN 1Vpp |
7 | n.c. | -120° or -90° 1Vpp * |
8 | n.c. | US_11 V (supply) |
9 | Temp._GND | n.c. |
10 | COS + (S1) | n.c. |
11 | SIN + (S2) | n.c. |
12 | REF + (R1) | n.c. |
13 | n.c. | REFSIN 1Vpp |
14 | n.c. | REF -120° or -90° 1Vpp * |
15 | n.c. | GND (supply) |
*) The angle must be configured