X07 – External braking resistor

DANGER

Serious risk of injury due to high electrical voltage!

A life-threatening voltage of 890 V DC remains present at the RB+ and RB- terminals even after the device has been shut down.

  • After shutdown, wait
    15 minutes
    for the AX5160/AX5172
    30 minutes for the AX5190/AX5191
    45 minutes for the AX5192/AX5193
  • Check the voltage

Notice

Damage to devices

Connect the PE connection of the external braking resistor to the central grounding bar.

AX5160 and AX5172

X07 – External braking resistor 1:

Terminal point

Connection

RB +

Ext. braking resistor +

RB -

Ext. braking resistor -

AX5190 and AX5191

X07 – External braking resistor 2:

Terminal point

Connection

RB +

Ext. braking resistor +

RB -

Ext. braking resistor -

AX5192 and AX5193

X07 – External braking resistor 3:

Terminal point

Connection

RB +

Ext. braking resistor +

RB -

Ext. braking resistor -