Electrical data
Electrical data | AX5160 | AX5172 | AX5190 | AX5191 | AX5192 | AX5193 |
|---|---|---|---|---|---|---|
Rated output current (1) | 60 A | 72 A | 90 A | 110 A | 143 A | 170 A |
Minimum rated motor current at full current resolution | 16 A | 20 A | 25 A | 30 A | 35 A | 40 A |
Peak output current (2) | 120 A | 144 A | 180 A | 180 A | 215 A | 221 A |
Rated supply voltage | 3x 400-10%…480+10% V AC | |||||
Max. DC link voltage | 890 V DC | |||||
Rated apparent power 480 V AC |
|
|
|
|
|
|
Power loss (3) | 830 W | 1010 W | 1300 W | 1600 W | 2100 W | 2500 W |
Min. braking resistance | 13 Ω | 13 Ω | 10 Ω | 10 Ω | 6.5 Ω | 6.5 Ω |
Max. braking power | 52 kW | 52 kW | 67 kW | 67 kW | 103 kW | 103 kW |
Mains chokes (4) |
| AX2090-ND50-xxxx | ||||
--- | --- | -0090 | -0110 | -0143 | -0170 | |
Mains filter (4) |
| AX2090-NF50-xxxx | ||||
integrated | -0100 | -0150 | -0150 | -0180 | ||
DC link capacitance | 900 µF | 1060 µF | 2120 µF | 3180 µF | 4240 µF | |
SCCR value | 5 kA | 10 kA | ||||
(1) With a rated supply voltage of 480 V AC, the rated current must be reduced by 10% or the ambient temperature reduced to ≤35°C. The specified values apply for an output rotational frequency > 5 Hz
(2) Irms for max. 3 s with a preload of max. 70% of the rated current
(3) S1 mode, including power supply unit, without brake chopper
(4) Required for compliance with EN 61800-3 (EMC product standard) C3 (industrial
environment) with a maximum motor cable length of 25 m.
SCCR value:
10 kA