Max. cable lengths including extensions
Rated motor voltage up to 400 V AC
Motor choke | AX5101…AX5112, AX52xx | AX5118, AX5125 | AX5140 | |||
|---|---|---|---|---|---|---|
C2 1) | C3 | C2 1) | C3 | C2 | C3 | |
Without | <25 m | <25 m | <25 m | <25 m | - | <30 m |
AX2090- | <100 m | <100 m | - | - | - | - |
AX2090- | - | - | <50 m | <50 m | - | - |
1) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0014.
2) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0032.
![]() | Sensitive sensors In exceptional cases (sensitive sensors, etc.) it can be necessary to use a motor choke even for motor cable lengths <25 m. |
Rated motor voltage up to 480 V AC
Motor choke | AX5101…AX5112, AX52xx | AX5118, AX5125 | AX5140 | |||
|---|---|---|---|---|---|---|
C2 1) | C3 | C2 2) | C3 | C2 | C3 3) | |
Without | <20 m | <20 m | <20 m | <20 m | - | 4) |
AX2090- | <100 m | <100 m | - | - | - | - |
AX2090- | - | - | <50 m | <50 m | - | - |
1) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0014.
2) For compliance with EN 61800-3 only with mains filter AX2090-NF50-0032.
3) C3 with up to 70 m without mains choke possible for devices with order number AX5140-0000-1202.
4) Please contact our applications department
In exceptional cases (sensitive sensors, etc.) it can be necessary to use a motor choke even for motor cable lengths <20 m.
To keep line perturbations (distortion reactive power) as low as possible, a mains choke should always be used.
![]() | Malfunction in residential areas Mains chokes are products with restricted availability in accordance with EN 61800-3. The products may cause radio interference in residential areas. In this case, necessary measures must be taken by the operator. |
Rated motor voltage up to 480 V AC
Servo drive | Category C2 | Category C3 | ||
|---|---|---|---|---|
| with mains filter | with mains filter and mains choke | without mains filter and without mains choke | with mains filter and mains choke |
AX51601) | max. 10 m | max. 25 m | max. 25 m | max. 50 m |
AX51722) | max. 10 m | max. 25 m | max. 25 m | max. 50 m |
AX51903) | --- | max. 10 m | --- | max. 25 m |
AX51914) | --- | max. 10 m | --- | max. 25 m |
AX51925) | --- | max. 10 m | --- | max. 25 m |
AX51936) | --- | max. 10 m | --- | max. 25 m |
For compliance with EN 61800-3 only in conjunction with the following accessories:
1) Mains filter AX2090-NF50-0063 and mains choke AX2090-ND0060
2) Mains filter AX2090-NF50-0100 and mains choke AX2090-ND0072
3) Mains filter AX2090-NF50-0100 and mains choke AX2090-ND0090
4) Mains filter AX2090-NF50-0150 and mains choke AX2090-ND0110
5) Mains filter AX2090-NF50-0150 and mains choke AX2090-ND0143
6) Mains filter AX2090-NF50-0180 and mains choke AX2090-ND0170
To keep line perturbations (distortion reactive power) as low as possible, a mains choke should always be used.
![]() | Malfunction in residential areas Mains chokes are products with restricted availability in accordance with EN 61800-3. The products may cause radio interference in residential areas. In this case, necessary measures must be taken by the operator. |