Connection of several servo drives to form a drive system

Connection of several servo drives to form a drive system 1:

Drive system with UL approval

Please note the configuration example in chapter 5.2.4.

CAUTION

Destruction of the devices

The connection sequence of the devices is not arbitrary. The rated sum current of the device must decrease from the mains supply onwards. AX5112, AX5106, AX5203, AX5201 = OK
AX5201, AX5112, AX5203 ≠ OK

All devices in a drive system are always to be disconnected from and reconnected to the supply network together (emergency shutdown, mains contactor etc.).

CAUTION

Danger for persons and equipment

Note the rated sum current of the connected devices.

According to CE, the current-carrying capacity of the power busbars of the AX-Bridge is limited to 85 A.

CAUTION

Destruction of the external braking resistor

An external braking resistor may not be connected to the X02 terminal point (DC link) in a drive system. Use an external brake module AX5021 for this.