P-x-0204 Power management control word

This parameter is used to enable / disable some features of the power management.

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min. Value

0

Default

9

Max. Value

127

Unit

-

EtherCATState

PreOp

Cyclic transfer

No

Device parameter

Yes

Related to interface revision

changed from Rev. 210


P-x-0204 Power management control word 1:

Included in the “Parameter Set Switching” function group!

This IDN exists as P-0-0204 - P-7-0204.

Parameter structure

Bit

Description

0

Internal brake resistor

0 = disabled
1 = enabled

1

DC link interface check

0 = DC link interface check active
1 = DC link interface check disabled

2

Umains monitoring

0 = Enable Umain monitoring
1 = Disable Umain monitoring

3

Umains phase error detection

0 = disabled
1 = enabled

4

Long filter time for Umains phase error detection
t = 5 s

0 = disabled
1 = enabled

5

Umains voltage down to 18V

0 = disabled
1 = enabled

6

Enable external ADC filter

0 = disabled
1 = enabled

7

DC link voltage monitoring (from Rev. 210)

0 = Enable dc link voltage monitoring
1 = Disable dc link voltage monitoring

8

Umains failure monitoring – device protection (from Rev. 210)

0 = Enable Umains failure monitoring
1 = Disable Umains failure monitoring

9

Power supply type (from Rev. 214)

10

reserved

11

Power supply type monitoring (from Rev. 214)

12

Periphery voltage monitoring (from Rev. 214)

13-15

reserved (from Rev. 214)