S-0-0200 Heatsink warning temperature

When the heatsink temperature exceeds the warning temperature value, the drive sets the warning bit for heatsink overtemperature in C2D (IDN S-0-0012).

Attributes

Name

Value

Datatype

udec

Data length in bit

16

Decimal point

1

Min value

60.0

Default

70.0

Max value

80.0

Unit

C°

Changeable in EtherCAT state

No

Cyclic transfer

No

Device parameter

Yes

Related to interface revision

No

S-0-0200 Heatsink warning temperature 1:

For further information please look into the involved IDN:

S-0-0012