Resetting the modulo error
The following figure shows channel B with modulo error F351.
The modulo error F350 / F51 can be reset using the System Manager / TCDriveManager or the PLC.
Reset with the System Manager
- Select the device “AX5203” (1).
- Open the TCDrivemanager (2).
- Cancel the EtherCAT error with “Change Phase – Clear Error” (3).
- Select item “Modulo value” (4).
- Set “Schedule modulo init data saving (PreOp->SaveOp” (5) to “Yes”.
- Set the EtherCAT status to “Op” (3).