Example for a vertical travel drive
The task
A load of 1000 kg is to be lowered by 1 m within 6 s.
Procedure
- Calculation of the potential load
- Calculation of the lowering time


![]() | Differentiation between peak and continuous load: Long braking times (> 1 s) no longer represent a peak load but a continuous load. Therefore, the continuous load must be added directly when calculating the braking power. Please note: For very short braking times (<1 s), the time can be considered in relation to the total cycle time.^t |