P-0-0341

Use the "Gantry brake configuration" parameter to configure the Gantry Brake function in the control loop of the servo drive. Instead of "Emergency stop deceleration" in parameter S-0-0429, for each braking operation the force is limited to the value set in parameter P-0-0341 "Gantry brake configuration".

P-0-0341 1:

Error state "Torque Off"

If an axis switches to the error state "Torque Off", the Gantry Brake can only be moved with the error-free axis. Due to the mechanical design, the force usually has to be limited in this case.

Switching off the speed controller I component reduces the tendency of the control to oscillate, leaving a braking force proportional to the speed deviation.

P-0-0341 2:

The Gantry Brake is activated if the device or the channel of an AX52xx receives an error.

Reaction of the servo drive

Reaction to the error < 100 µs: