FD5E, Device rated current too high for single phase supply.

Device rated current too high for single phase supply. Change power supply type (AC1) or P-0-0093

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

FD5E

64862

Class

Type

Error

Runtime error

Standard Reaction

Reset

Nc handling

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

Power supply type is wrong in P-0-0204.

Set power supply type to 3 phases (AC 3) in the IDN P-0-0204 bit 9 and bit 10.

Power supply type is single phase (AC 1)

Check in the IDN P-0-0093 whether you need to enter a derating.