FD29, Invalid gain scheduling characteristic data

Invalid gain scheduling characteristic data

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

FD29

64809

Class

Type

Error

Parameter error

Standard Reaction

Reset

The power stage is already switched off

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

Current Values are not in increasing order

The current values must be parameterised in a strictly monotonously increasing manner, i.e. every current value must be higher than the previous one

Current or proportial gain values are not within the permissible range

Check limitations