FAB6, Feedback "MES": Output voltage too low

The amplitude monitoring has determined the minimum value of the MES output voltage.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

FAB6

64182

Class

Type

Error

Runtime error

Standard Reaction

Reset

Open loop ramp

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

The MES cabling is faulty.

Please check the cabling (screen connection, connection hardware, lines and correct attachment of the connectors).

The MES is faulty.

Please replace the motor.

The amplitude monitoring is not optimally parametrized.

Please check the parametrization of the amplitude monitoring in IDN "P-0-0150".

An unknown hard- or software error has occurred.

Disconnect the servo drive from the mains (including the 24 V power supply) and start a new attempt. If this error occurs repeatedly, please call the Beckhoff branch office that is responsible for you.

Further Information

AX5000_IDN-Description: "P-0-0150 -->Process channel-->Data-->MES-->Amplitude monitoring-->Min limit"