F7C6, Feedback parameter channel initialization error (BiSS).

The initialization of the feedback parameter channel has failed (BiSS): Parameter error.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

F7C6

63430

Class

Type

Error

Runtime error

Standard Reaction

Reset

Open loop ramp

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

The feedback line is defective.

Check the line.

Wrong feedback system.

Enter the correct feedback system.

The feedback system is defective.

Check the feedback system.

Further Information

See also diagnostic message "F739"