F782, Feedback "general": Initialization failed

The initialization of the feedback parameter channel has failed (EnDat).

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

F782

63362

Class

Type

Error

Runtime error

Standard Reaction

Reset

The power stage is already switched off

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

The feedback line is defective.

Check the line.

Wrong feedback system.

Enter the correct feedback system.

The feedback system is defective.

Check the feedback system.

An unknown hard- or software error has occurred.

Disconnect the servo drive from the mains (including the 24 V power supply) and start a new attempt. If this error occurs repeatedly, please call the Beckhoff branch office that is responsible for you.