F739, Feedback "general": Wrong feedback
The expected feedback system could not be confirmed.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
F739 |
63289 |
Class |
Type |
---|---|
Error |
Parameter error |
Standard Reaction |
Reset |
---|---|
The power stage is already switched off |
Execute Reset-Command (S-0-0099). |
Possible Causes |
Solutions |
---|---|
Linear motor You have entered a feedback system in the IDN P-0-0150 that cannot be confirmed. |
Determine the correct feedback system and enter it in the IDN P-0-0150 |
Rotary motor: You have selected the wrong motor and thus possibly also the wrong feedback system. |
Select the correct motor. |
![]() | Please consider this note! If the manufacturer entered in the IDN P-0-0150 correlates to the actual manufacturer, please check the exact model designation. |
Further Information |
---|
AX5000_IDN-Description: "P-0-0150" |