F50D, A/D-Converter: DC-Link - Measuring error
The analog/digital converter has picked up an invalid signal during measurement of the external reference current for the DC link.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
F50D |
62733 |
Class |
Type |
---|---|
Error |
Runtime error |
Standard Reaction |
Reset |
---|---|
Nc handling |
Execute Reset-Command (S-0-0099). |
Possible Causes |
Solutions |
---|---|
EMC-Problems. |
Check the cable screening and screen connection of all cables to the devices. Check whether all components are earthed on the same potential. Check whether the AX5000 was securely attached to the metallic rear panel and whether the panel is earthed. |
There is an internal hardware error. |
Send the AX5000 to the Beckhoff branch office that is responsible for you. |