F441, Dynamic SyncManager: Required SyncManager not enabled.
Dynamic SyncManager: Required SyncManager not enabled.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
F441 |
62529 |
Class |
Type |
---|---|
Error |
Runtime error |
Standard Reaction |
Reset |
---|---|
Closed loop ramp |
Execute Reset-Command (S-0-0099). |
Possible Causes |
Solutions |
---|---|
The drive operation mode has changed to a mode which uses the dynamic sync manager while the dynamic sync manager are not enabled. |
Check if your application activates the dynamic sync manager. |