F407, EtherCAT slave controller (MDT): Syncmanager parameter

The EtherCAT process data communication cannot be started due to invalid sync manager parameterization.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

F407

62471

Class

Type

Error

Parameter error

Standard Reaction

Reset

The power stage is already switched off

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

A data type in the process image was changed.

Check the data types in the process image.

An unknown hard- or software error has occurred.

Disconnect the servo drive from the mains (including the 24 V power supply) and start a new attempt. If this error occurs repeatedly, please call the Beckhoff branch office that is responsible for you.