F360, Initialization of the device: failed

The initialization of the AX5000 has failed.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

F360

62304

Class

Type

Error

Runtime error

Standard Reaction

Reset

Closed loop ramp

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

The digital output was used more than once.

Check the digital output assignment.