F121, Command "Motor and feedback check": No hardware enable

The execution of the "Check motor and feedback" command has failed because the configured hardware enable is missing.

Diagnostic Code (Hex.)

Diagnostic Code (Dez.)

F121

61729

Class

Type

Error

Command error

Standard Reaction

Reset

Abort the procedure command execution.

Execute Reset-Command (S-0-0099).

Possible Causes

Solutions

The hardware enable of the corresponding terminal point on plug "X06" is missing.

Apply the hardware enable (IDN P-0-0400).