F104, Axis state machine: NC error handling - Timeout
With NC error handling activated (P-0-0350), the AX5000 was not stopped by the NC within the parametrized time period (P-0-0351).
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
F104 |
61700 |
Class |
Type |
---|---|
Error |
Runtime error |
Standard Reaction |
Reset |
---|---|
Closed loop ramp |
Execute Reset-Command (S-0-0099). |
Possible Causes |
Solutions |
---|---|
The selected time period is too short. |
Increase the time period if your application allows this. |
The movement is too complex for the parametrized time period. |
Program a movement that is suitable for the time period. |
Further Information |
---|