F0A0, FPGA error: configuration could not be loaded
The internal FPGA configuration could not be loaded.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
F0A0 |
61600 |
Class |
Type |
---|---|
Error |
Bootloader error |
Standard Reaction |
Reset |
---|---|
The power stage is already switched off |
A reset is not possible. A fatal hard- or software error occured and the transition PreOp->SafeOp is blocked. |
Possible Causes |
Solutions |
---|---|
The firmware file is defective. |
Exchange the defective firmware file to a valid one. |
There is an internal hardware or software error. |
Disconnect the servo drive from the mains (including the 24 V power supply) and start a new attempt. If this error occurs repeatedly, please call the Beckhoff branch office that is responsible for you. |